Self-monitoring and fail-safe control unit for the monitoring of gas, oil and coal flames with DURAG UV, UV+IR or IR- flame sensors, primarily in multiple-burner furnaces |
Features |
|
Suitable for intermittent operation, continuous operation and 72-hour operation as per TRD 604 |
|
Optional parallel operation of two flame sensors in any combination: UV/UV, UV/IR or IR/IR |
|
Three different settings supported for various modes (e.g. dependent on fuel or combustion technology), automatic activation by burner management system |
|
Plain text display |
|
Applications |
|
Power stations | |
Chemical industry |
|
Refineries |
|
Cement plants |
|
Waste incinerators |
|
Steam generators |
|
Heating plants |
|
Operational mode |
intermittent operation, continuous operation and 72-hour operation without permanent supervision |
Safety |
self-monitoring and fail-safe in conjunction with a control unit/burner control |
Power supply |
24/48 VAC or VDC, 115/230 VAC |
Protection |
IP00 |
Flame relay |
1x switch-over contact, 230 VAC, 2A |
Status relay |
1x switch-over contact, 230 VAC, 2A |
Switching threshold |
00...99 |
Safety time |
1 ... 5,5s |
Pre-configurable combinations of switching threshold and safety time |
3 |
Flame sensor connection |
1 or 2 (parallel) |
Display |
Alphanumerische LCD-Display |
Flame intensity |
0/4...20 mA |
Flame signal |
0/4...20mA |
Perm. ambient temperature |
-20...+60°C |
Dimensions |
19" plug-in module, 3 RU, 21 HP |
Weight |
approx. 1 kg |
Self-monitoring and fail-safe control unit for the monitoring of gas, oil and coal flames with DURAG UV, UV+IR or IR flame sensors, primarily in single burner furnaces |
Features |
|
suitable for intermittent operation, continuous operation and 72-hour operation according to TRD 604 |
|
LED display |
|
installation on DIN-rail |
|
Applications |
|
Power stations | |
Chemical industry |
|
Refineries |
|
Cement plants |
|
Waste incinerators |
|
Steam generators |
|
Heating plants |
|
Operational mode |
intermittent operation, continuous operation and 72-hour operation without permanent supervision |
Safety |
self-monitoring and fail-safe in conjunction with a control unit/burner control |
Power supply |
24 VDC |
Protection |
IP20 |
Flame relay |
1x NO contact, 230 VAC, 2A |
Status relay |
1x NO contact, 230 VAC, 2A |
Installation |
TS 35 DIN-rail |
Safety time |
1 s |
Configurable switching thresholds |
1 |
Switching thresholds |
0...9 |
flame sensor |
1 |
Display |
LED |
Flame intensity |
0/4...20 mA |
Perm. ambient temperature |
-20...+60°C |
Dimensions |
100 x 75 x 118 mm (WxHxD) |
Weight |
approx. 0.45 kg |