DURAG D-HG 400 High Energy Ignition Device
The D-HG 400 high energy ignition device is suitable for the ignition of gas or liquid fuels in industrial burners of any capacity |
Features |
|
Ignition of liquid or gaseous fuels with large power ratings |
|
Compact design: control unit and ignition lance form one unit |
|
Ignites even heavy oil no. 6 |
|
Special designs for potentially explosive atmospheres are available |
|
Special design with battery operation | |
Special design for swivelling burner | |
No wear because thyristor controlled | |
20 ignition sparks á 4.5 J per second | |
Ignition feedback signal via integrated LED or potential-free relay output | |
Suitable as "Ignitor Class 3 Special“ in accordance with NFPA 8501 and NFPA 8502 | |
Applications |
|
Chemical industry |
|
Refineries |
|
Cement plants |
|
Waste incinerators |
|
Steam generators |
|
Heating plants |
|
|
Power supply |
115 / 230 VAC, 50 / 60 Hz |
Power consumption |
220 VA |
Zündspannung/ -energie |
1500 V / 4.5 J |
Power-on time |
300 s (ESD 50%) |
Perm. ambient temperature |
-20…+60°C |
Protection |
IP 54 |
Switching performance |
250 VAC / 4A |
Display |
LED |
Max. temperature of the ignition tip |
600°C permanent |
Operational life of the ignition tip |
106 sparks |
Ignition frequency |
20 sparks/s for 1 min, 5 sparks/s thereafter |
Dimensions |
108 x 188 x 237 mm (LxWxH) |
Weight (approx.) |
D-HG 400-50 with 3 m lance: 9.0 kg |
More Info Price
DURAG D-HG 55 Electronic Ignition Transformer
D-HG 55 Electronic Ignition Transformer
The D-HG 55 electronic ignition transformer is suitable for the ignition of gases and liquid fuels in small burners |
Features |
|
Ignition of oil and gas |
|
High-performance and reliable ignition |
|
Simple to use and installion |
|
Robust enclosure for industrial use |
|
100 ignition sparks/second with a mains frequency of 50Hz, 120 ignition sparks/second with a mains frequency of 60Hz | |
Suitable as "Ignitor Class 3 Special“ in accordance with NFPA 8501 and NFPA 8502 |
|
Applications |
|
Chemical industry |
|
Refineries |
|
Cement plants |
|
Waste incinerators |
|
Steam generators |
|
Heating plants |
|
Power supply |
115 / 230 VAC, 50 / 60 Hz |
Power consumption |
15 VA |
Ignition voltage |
5000 V |
Power-on time |
50% |
Perm. ambient temperature |
-20 … +60°C |
Protection |
IP 65 |
Dimensions |
100 x 100 x 80 mm (LxWxD) |
Weight |
approx. 0.7 kg |